171
Reference Manual
00809-0100-4570, Rev AC
Appendix B: Product Certifications
January 2015
Product Certifications
Conditions of Certification (X):
1. The apparatus is not capable of withstanding the 500V test as defined in Clause 6.3.13
of EN60079-11:2012. This must be considered in any installation.
2. The Rosemount 3300 Series enclosure is made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be taken to protect it from
impact or abrasion if located in zone 0.
3. The probes may contain plastic materials greater than 4 cm
2
or be coated with plastic
and these can present an electrostatic risk if rubbed or placed in a fast moving air flow.
4. The probes may contain light alloys which can present a risk from frictional ignitions.
Care should be taken to protect them from mechanical impact during use or
installation.
I7 Intrinsic safety:
Certificate: IECEx BAS 12.0062X
Ex ia IIC T4 (T
a
60 °C) IP66
U
i
= 30 V, I
i
= 130 mA, P
i
= 1 W, C
i
= 0 nF, L
i
= 0 mH
Approval valid for HART option.
Conditions of Certification (X):
1. The apparatus is not capable of withstanding the 500V test as defined in Clause 6.3.13
of EN60079-11:2012. This must be considered in any installation.
2. The Rosemount 3300 Series enclosure is made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be taken to protect it from
impact or abrasion.
3. The probes may contain light alloys which can present a risk from frictional ignitions.
Care should be taken to protect them from mechanical impact during use or
installation.
4. The probes may contain plastic materials greater than 4 cm
2
or be coated with plastic
and these can present an electrostatic risk if rubbed or placed in a fast moving air flow.
5. The cable entry must use a suitable Certified Cable Gland which provides strain relief
and any unused openings to the equipment must be blanked off to maintain a degree
of protection of at least IP66.
N7 Type N approvals: non-sparking/intrinsic safety
Certificate: IECEx BAS 12.0061X
Ex ic nA IIC T4 Gc (-50 °C < T
a
< +70 °C)
Standards:
IEC 60079-0:2011, IEC 60079-11:2001,
IEC 60079-31:2008, IEC 60079-1:2007,
IEC 60079-26:2006